Description
Features
|
Applications
|
Heated & 85°F (30°C) Fan Cooled NEMA Enclosure with 120VAC Power for All Weather Conditions
The Altelix NF141208VFHA1-85 is deal for outdoor environments where temperatures vary between hot and cold. It is equipped with thermostat controlled heating and cooling systems to help keep your equipment within its operational temperature range.
200W Thermostat Controlled Heating System
This enclosure features a thermostat controlled 200W heating system. The heater turns on when the internal temperature reaches 43°F (6°C) and turns off when it rises to 59°F (15°C). The heater is mounted below the equipment plate and wired internally so leaves the interior space and power outlets available for your equipment.
Thermostat Controlled Cooling Fan
This enclosure features two 4" vents and a thermostat controlled cooling fan which is set to 85°F (30°C) for additional cooling. The fan turns on when the internal temperature reaches 85°F (30°C) and turns off when it drops to 59°F (15°C). Rain shrouds keep rain water from entering the enclosure while allowing ventilation for your equipment.
120VAC Power Outlets
This enclosure provides four pre-wired 120VAC power outlets and a quick-connect terminal strip for easy wiring by a qualified installer.
Extreme Protection Built to Last
This rugged JIC style NEMA box is molded from durable UV stable and corrosion resistant fiberglass reinforced polyester (FRP) with a UL94-5V flame rating. The FRP material is dent-proof, non-conductive and RF transparent for compatibility with wireless equipment. It can be easily drilled and modified by the installer as needed. It features a gasketed door with stainless steel continuous hinge and stainless steel quick release latches with padlock hasps. The generous size of this enclosure and the extended lid accommodate a wide range of equipment.
Cable Glands
The enclosure features two unique PG-16 cable glands with a closed inner seal. They are installed in the open ports to maintain the NEMA rating of the enclosure when not in use. When required for use, simply punch a hole through the inner membrane, run your cables and tighten for a water-tight seal. To provide power to the enclosure a 1/2" Liquid-Tight fitting as well as a PG16 Cable Gland are included.
Removable Terminal Block
This enclosure features our 120VAC top entry terminal block. It is easily removable which helps simplify on-site wiring. It can accept wires sizes from 12 to 18 AWG. The wires are secured by side terminal screws.
Mounting
Stainless steel brackets are included for secure wall mounting. Optional flange and pole mounting kits are available. See available accessories when adding to cart.
Customization
We offer custom enclosures for WiFi equipment, DIN Mount Industrial Controls, Telephone Call Boxes, IP Phones, Security & Safety, Building Automation and More. Options include equipment mounting plates, DIN rails, AC/DC power, vents, cooling fans, heaters. We also offer full customization, engineering and on-site CNC machining of enclosures and associated equipment, all with quick turnaround time. Please contact us with your unique requirements.
Technical Specifications
Material | Fiberglass Reinforced Polyester |
Color | Gray |
Voltage | 120VAC |
Max Load | 15A @ 120VAC |
Terminal Block Wire Range | 12-18 AWG |
Terminal Block Wire Strip Length | 6-7mm |
Cooling Fan Turn-On Temperature | 85°F (30°C) ±6°F |
Cooling Fan Turn-Off Temperature | 59°F (15°C) ±9°F |
Heater Turn-On Temperature | 43°F (6°C) ±5°F |
Heater Turn-Off Temperature | 59°F (15°C) ±5°F |
Heater Power | 200 Watts |
Outer Dimensions | 15.7 x 13.8 x 10.1 Inches (401 x 352 x 258 mm) |
Inner Dimensions* | 13.0 x 11.0 x 5.0 Inches (330 x 279 x 127 mm) |
Mounting Plate Material | 0.10 in (2.5 mm) Aluminum |
Mounting Plate Dimensions | 10.9 x 12.8 in. (276 x 324 mm) |
Weight | 13.4 lbs. (6.1 kg) |
Ratings | NEMA Type 3R, 3RX / IP24 |
Flame Rating | UL94-5V |
*See drawing for detailed dimensions of maximum space available for equipment. |